MENU

Party Walls

Understanding Accessibility: Notable Changes in the 2022 New York City Building Code

As of November 7, 2022, the 2022 edition of the New York City Building Code is now in effect. As designers begin to work with the updated code, our accessibility consultants have been getting a lot of questions about what has changed from the requirements in the 2014 edition of the code.

Cover of the New York City Building Code.While it is important to read through the new code in its entirety to ensure compliance with all updated criteria, we have compiled a list of some changes related to accessibility that designers should be aware of, below.

SECTION BC 1106: Parking and Passenger Loading Facilities

8 Electric Vehicle Charging Stations

While the 2014 edition of the code was silent on specific requirements for electric vehicle parking, the 2022 edition provides scoping and technical criteria for charging stations and the parking spaces serving those stations. Where EV charging is provided for common use, at least 5%, but no less than one of each type of EV station must be accessible.

8.2 Electric Vehicle Charging Space

At each accessible electrical vehicle charging station, the parking space is required to comply with the criteria for van accessible parking spaces in ICC A117.1-2009 Sections 502.2 through 502.5.

SECTION BC 1107: Dwelling Units and Sleeping Units

2.1, Exception 1.2 Type B+NYC Unit Doors and Doorways

At balconies, patios, and/or terraces greater than 24 inches in clear depth, maneuvering clearance is required on both the interior and exterior side of the door. Previously, where the dimensions of the balcony were less than the required maneuvering clearance, the exterior side of the door was exempted from clearance requirements.

2.1, Exception 6.2 Bathroom and Toilet Room Doors

Maneuvering clearance is required on both sides of bathroom and toilet room doors. Unless a Type A toilet and bathing room is provided in a Type B+NYC unit, all doors to toilet and bathing rooms are required to provide maneuvering clearance on both the exterior and interior side of the door. Previously, maneuvering clearance on the interior side of an Appendix P bathroom door was not required.

2.2 Type B+NYC Unit Toilet and Bathing Rooms

One of the most notable changes is the elimination of Appendix P, which previously contained the bathroom criteria for Type B+NYC dwelling units. The 2022 edition of the code has relocated the criteria previously contained in Appendix P within Chapter 11.

2.7, Exception 1 Type B+NYC Unit Storage

A 60 inch turning space is now required where dwelling unit closets are more than 48 inches in depth.

SECTION BC 1109: Other Features and Facilities

7.2 Destination-oriented Elevators

Scoping and technical criteria for destination-oriented elevators can now be found within Chapter 11. Requirements for accessibility function buttons, audio output, display screens, and other elements of destination-oriented elevators are provided.

9.3 Cycle Storage

Where cycle storage is provided, 10% of the total number, but not less than one, shall be a minimum of 86 inches long and 42 inches wide to accommodate the storage of an accessible cycle. Previously, 5% of storage spaces were required to be accessible, but no specific technical criteria for accessible bicycle storage spaces was provided.

11 Seating at Tables and Counters and Work Surfaces

Where seating or standing spaces are provided at fixed or built-in tables, counters, or work surfaces, at least 10% of the total number of spaces, but not less than one of each type, shall be accessible. Previously, 5% of seating or standing spaces were required to be accessible.

17 Refuse Disposal, Refuse Recyclable, and Refuse Storage Rooms

Specific technical criteria for trash rooms are now provided. Trash rooms must provide turning space, a clear floor space beyond the door swing, maneuvering clearance at the door, and accessible operable parts.

Exception: The alternative trash room design previously detailed in a DOB memo has been incorporated into the exception to trash room criteria. Trash rooms that have an automatic door with a 36 inch minimum clear opening width, an occupancy sensor, and all controls, chutes, and recycling bins within reach are not required to provide turning space or maneuvering clearance within the trash room.

SECTION BC 1111: Signage

1 Signs

Dynamic Symbol of Accessibility.At locations listed at this section, the dynamic accessibility symbol replaces the International Symbol of Accessibility (ISA).

Note that the dynamic accessibility symbol is required at refuse/trash rooms. The ISA was not previously required at trash rooms.

 

Written by:

Photo of Camilo Vasquez.

 

 

Camilo Vasquez, Senior Accessibility Consultant at SWA

 

 

Theresa Dandrea

 

 

Theresa D’Andrea, Senior Accessibility Consultant at SWA

 

 

Share This Entry

Comments are closed.

Leave a Reply

Your email address will not be published. Required fields are marked *


The reCAPTCHA verification period has expired. Please reload the page.

The owner of this website has made a commitment to accessibility and inclusion, please report any problems that you encounter using the contact form on this website. This site uses the WP ADA Compliance Check plugin to enhance accessibility.